SINGLE PACKAGE ROOFTOP UNITS WITH X-VANE™ FAN TECHNOLOGY: GAS HEATING/ELECTRIC COOLING (RGV) AND ELECTRIC COOLING/OPTIONAL ELECTRIC HEAT (RAV) 3 – 6 TON

RGV/RAV

Features

The new 3 to 6 Ton RGV/RAV series rooftop units (RTU) with X-VaneTM Fan Technology provides value added benefits never seen in this type of equipment before. New major design features include:

  • Patent pending, the industry’s first beltless direct-drive vane axial fan for rooftop units with electric commutated variable speed motor.

  • Reliable fixed speed scroll compressor on 3-5 ton sizes and 2 stage scroll technology on 6 ton sizes.

  • Upgraded unit control board with intuitive indoor fan adjustment.

  • Reliable copper tube/aluminum fin condenser coil with 5/16-in. tubing to

    help reduce refrigerant charge versus prior designs.

  • New outdoor fan system with rugged, lightweight high impact composite

    fan blade.

    Installation ease

    All RGV/RAV units are field convertible to horizontal air flow, which makes it
    easy to adjust to unexpected job site complications. RGV/RAV rooftop units up to 6 tons are specifically designed to fit on our existing roof curbs dating back to 1989 for worry-free original fit. Also, our large control box gives you room to work and room to mount accessory controls. Intuitive controls make setting up the required fan speed simple and accurate. Access to the blower section is no longer needed with the new design.

    Easy to maintain

    With the new Vane Axial fan and direct drive ECM motor, there is no longer a need to adjust belts or pulleys as in past designs. This frees up maintenance and installation time.

    Easy access handles provide quick and easy access to all normally serviced components. Our “no-strip” screw system has superior holding power and guides screws into position while preventing the screw from stripping the unit’s metal.

    Sloped, corrosion resistant composite drain pan sheds water and won’t rust.

    RGV units are designed with a naturally draining heat exchanger. Unlike positive pressure heat exchangers, this does not need to be periodically, manually drained. This saves labor and maintenance expense.

    Easy to use

    The newly re-designed Unit Control Board puts all connections and troubleshooting points in one convenient place. Most low voltage connections are made to the same board for easy access. Setting up the fan is made simple by an intuitive switch and rotary dial arrangement. RGV/RAV rooftops have high and low pressure switches, a filter drier, and 2-in. filters standard.

    X-Vane Fan Technology

    Direct drive X-Vane Fan Technology indoor fan system uses vane axial fan design and electrically commutated motors. This new Vane Axial design over past belt drive systems has 75% fewer moving parts, uses up to 40% less energy and has no fan belts, blower bearings, or shaft.

    Design features include:

  • Single-stage units deliver SEERs up to 14.0 and EERs up to 11.8. Two-stage units deliver IEERs up to 15.2 and EERs up to 11.2.

  • All models are capable of either vertical or horizontal airflow.

  • RGV/RAV rooftop units (RTU) were designed by customers for customers. With “no-strip” screw collars, handled access panels, and more the unit is easy to install, easy to maintain, and easy to use. Your new 3 to 6 ton RGV/RAV rooftop unit (RTU) provides optimum comfort and control from a packaged rooftop.

Features/Benefits

            Value-added features include:

  • Optional Hot Gas Re-Heat dehumidification system for improved part load humidity performance

  • R-410A refrigerant

  • Single point gas and electrical connections

  • 3 to 5 ton models use fixed refrigerant metering devices and 6 ton models use a TXV

  • Scroll compressors with internal line-break overload protection

    Operating efficiency and flexibility

    The RGV/RAV rooftops exceed ASHRAE (American Society of Heating, Refrigerating, and Air-Conditioning Engineers) 90.1-2016, IECC1 (International Energy Conservation Code) IECC-2018 minimum efficiency requirements.

    Field convertible airflow

    All RGV/RAV 3 to 6 ton units are field-convertible to horizontal airflow, which makes it easy to adjust to unexpected job site complications.

    Comfort control

    Our patented Hot Gas Re-Heat dehumidification system is an all-inclusive factory-installed option on gas heating/electric cooling and electric cooling/electric heat models. This system provides reliable, flexible operation to meet indoor part load sensible and latent requirements.

Unit Performance Data

UNIT PERFORMANCE DATA - Single Stage Cooling/Single Stage Circuit
UNIT Nominal Tons COOLING GAS HEATING Unit Dimensions         H x W x L Shipping Weight lb. [kg]
Net Cap. (Btuh) EER SEER IEER w/ 2-speed Indoor Fan Motor Input Cap. (Bthu) Stage 2 Thermal Efficiency (%)
RGV036*^DA0AAA 3 34,400 11.5 14.0 N/A 65,000 - 90,000 80-82
33 3/8" x 46 5/8" x 74 3/8"
522 [237]
RGV048*^DA0AAA
4 47,000 11.6 14.0 N/A 65,000 - 130,000 80-82
33 3/8" x 46 5/8" x 74 3/8"
583 [265]
RGV060*^DA0AAA
5 58,500 11.0 14.0 N/A 65,000 - 130,000 80-82
33 3/8" x 46 5/8" x 74 3/8"
596 [271]
UNIT PERFORMANCE DATA - Two Stage Cooling/Single Circuit
UNIT Nominal Tons COOLING GAS HEATING Unit Dimensions         H x W x L Shipping Weight lb. [kg]
Net Cap. (Btuh) EER SEER IEER w/ 2-speed Indoor Fan Motor Input Cap. (Bthu) Stage 2 Thermal Efficiency (%)
RGV072*^DA0AAA 6 70,000 11.0 N/A 15.0 67,000-150,000 80-81
41 3/8" x 46 5/8" x 74 3/8"
647 [294]
UNIT PERFORMANCE DATA - Single Stage Cooling/Single Circuit
UNIT Nominal Tons COOLING Unit Dimensions H x W x L Shipping Weight lb. [kg]
Net Cap. (Btuh) EER SEER Total Power (kW) IEER w/ 2-speed Indoor Fan Motor
RAV036*^DA0AAA 3 34,400 11.7 14 2.9 N/A
33 3/8" x 46 5/8" x 74 3/8"
477 [217] 
RAV048*^DA0AAA
4 47,000 11.8 14 4.0 N/A
33 3/8" x 46 5/8" x 74 3/8"
538 [244] 
RAV060*^DA0AAA
5 58,500 11.2 14 5.2 N/A
33 3/8" x 46 5/8" x 74 3/8"
551 [250] 
UNIT PERFORMANCE DATA - Two Stage Cooling/Single Circuit
UNIT Nominal Tons COOLING Unit Dimensions H x W x L Shipping Weight lb. [kg]
Net Cap. (Btuh) EER SEER Total Power (kW) IEER w/ 2-speed Indoor Fan Motor
RAV072*^DA0AAA 6 70,000 11.2 N/A 5.7 15.2
41 3/8" x 46 5/8" x 74 3/8"
602 [273] 

* Indicates Unit voltage: K = 208/230-1-60, H = 208/230360, L = 460360, S = 575360
^ See model nomenclature listing for gas heating options.
NOTE: BASE MODEL NUMBERS LISTED. SEE MODEL NOMENCLATURE LISTING FOR ADDITIONAL OPTIONS 

UNIT PERFORMANCE DATA — Single Stage Cooling /Single Circuit

Unit:
RGV036*^DA0AAA

Nominal Tons:
3

COOLING-Net Cap. (Btuh):
34,400

COOLING-EER:
11.5

COOLING-SEER:
14.0

COOLING-IEER w. 2-stage Indoor Fan Motor:
N/A

HEATING-Input Cap. (Btuh) Stage 2:
65,000 - 90,000

HEATING-Thermal Efficiency (%):
80-82

Unit Dimensions H x W x L:
33 3/8" x 46 5/8" x 74 3/8"

Shipping Weight lb. [kg]:
522 [237]

Unit:
RGV048*^DA0AAA

Nominal Tons:
4

COOLING-Net Cap. (Btuh):
47,000

COOLING-EER:
11.6

COOLING-SEER:
14.0

COOLING-IEER w. 2-stage Indoor Fan Motor:
N/A

HEATING-Input Cap. (Btuh) Stage 2:
65,000 - 130,000

HEATING-Thermal Efficiency (%):
80-82

Unit Dimensions H x W x L:
33 3/8" x 46 5/8" x 74 3/8"

Shipping Weight lb. [kg]:
583 [265]

Unit:
RGV060*^DA0AAA

Nominal Tons:
5

COOLING-Net Cap. (Btuh):
58,500

COOLING-EER:
11

COOLING-SEER:
14.0

COOLING-IEER w. 2-stage Indoor Fan Motor:
N/A

HEATING-Input Cap. (Btuh) Stage 2:
65,000 - 130,000

HEATING-Thermal Efficiency (%):
80-82

Unit Dimensions H x W x L:
33 3/8" x 46 5/8" x 74 3/8"

Shipping Weight lb. [kg]:
596 [271]

UNIT PERFORMANCE DATA — Two Stage Cooling /Single Circuit

Unit:
RGV072*^DA0AAA

Nominal Tons:
6

COOLING-Net Cap. (Btuh):
70,000

COOLING-EER:
11

COOLING-SEER:
N/A

COOLING-IEER w. 2-stage Indoor Fan Motor:
15.0

HEATING-Input Cap. (Btuh) Stage 2:
67,000-150,000

HEATING-Thermal Efficiency (%):
80-81

Unit Dimensions H x W x L:
41 3/8" x 46 5/8" x 74 3/8"

Shipping Weight lb. [kg]:
647 [294]

UNIT PERFORMANCE DATA — Single Stage Cooling /Single Circuit

Unit:
RGV036*^DA0AAA

Nominal Tons:
3

COOLING-Net Cap. (Btuh):
34,400

COOLING-EER:
11.5

COOLING-SEER:
14.0

COOLING-IEER w. 2-stage Indoor Fan Motor:
N/A

COOLING-Total Power (kW):
2.9

Unit Dimensions H x W x L:
33 3/8" x 46 5/8" x 74 3/8"

Shipping Weight lb. [kg]:
477 [217]

Unit:
RGV048*^DA0AAA

Nominal Tons:
4

COOLING-Net Cap. (Btuh):
47,000

COOLING-EER:
11.6

COOLING-SEER:
14.0

COOLING-IEER w. 2-stage Indoor Fan Motor:
N/A

COOLING-Total Power (kW):
4

Unit Dimensions H x W x L:
33 3/8" x 46 5/8" x 74 3/8"

Shipping Weight lb. [kg]:
538 [244]

Unit:
RGV060*^DA0AAA

Nominal Tons:
5

COOLING-Net Cap. (Btuh):
58,500

COOLING-EER:
11

COOLING-SEER:
14.0

COOLING-IEER w. 2-stage Indoor Fan Motor:
N/A

COOLING-Total Power (kW):
5.2

Unit Dimensions H x W x L:
33 3/8" x 46 5/8" x 74 3/8"

Shipping Weight lb. [kg]:
551 [250]

UNIT PERFORMANCE DATA — Two Stage Cooling /Single Circuit

Unit:
RGV072*^DA0AAA

Nominal Tons:
6

COOLING-Net Cap. (Btuh):
70,000

COOLING-EER:
11

COOLING-SEER:
N/A

COOLING-IEER w. 2-stage Indoor Fan Motor:
15.2

COOLING-Total Power (kW):
5.7

Unit Dimensions H x W x L:
41 3/8" x 46 5/8" x 74 3/8"

Shipping Weight lb. [kg]:
602 [273]